One (1) upholstery fabric sample, identified as Flame-No-More 100% Cotton (8.4 oz./sq. yd.), was received and tested in accordance with the Department of Transportation, Federal Aviation Administration Regulations for Compartment Interiors, Par. 25.853 (b), Vertical Test. The results are as follows:
The fabric sample submitted meets the minimum requirements of the above standard. The average burn length may not exceed 8.0 inches and the average afterflame time may not exceed 15.0 seconds.
If there are any questions or when we can be of further assistance, please let us know.
Karon S. Matkins
National Fire Protection Asssociation
Flame Resistant Textiles Test
(As Tested by Diversified Labs) see top of page
| Reference: |
Flammability Test Report
Lab Identification No. 3854
Invoice No. 8418 |
One (1) upholstery fabric sample, identified as Flame-No-More, 100% Cotton (8.0 oz./sq. yd.), was received and tested in accordance with the National Fire Protection Association No. 701, "Flame Resistant Textiles and Films, 1989 Edition, (Small Scale Test)". The results are as follows:
| Specimen Number |
After Flame |
Residual Flame |
Char Length |
| |
Length |
Width |
Length |
Width |
Length |
Width |
| 1 |
0.0 |
0.0 |
0.0 |
0.0 |
4.1 |
4.5 |
| 2 |
0.0 |
0.0 |
0.0 |
0.0 |
3.9 |
4.7 |
| 3 |
0.0 |
0.0 |
0.0 |
0.0 |
4.0 |
4.4 |
| 4 |
0.0 |
0.0 |
0.0 |
0.0 |
4.0 |
4.0 |
| 5 |
0.0 |
0.0 |
0.0 |
0.0 |
5.3 |
4.2 |
| |
| Average |
|
|
|
|
4.3 |
4.3 |
The fabric sample submitted meets the minimum requirements of the above standard. For fabrics whose weight is at least 6.0 oz./sq.yd., but does not exceed 10.0 oz./sq.yd., the average char length may not exceed 4.5 inches with no individual value exceeding 5.5 inches. Additionally, there may be no afterflame which exceeds 2.0 seconds and no residual flame.
If there are any questions or when we can be of further assistance, please let us know.
Sincerely,
Karon S. Matkins
Upholstered Furniture Action Council
Fabric Classification Test
(As Tested by Diversified Labs) see top of page
| Reference: |
Flammability Test Report
Lab Identification No. 3854
Invoice No. 8418 |
One (1) upholstery fabric sample, identified as Flame-No-More, 100% Cotton (8.4 oz./sq. yd.), was received and tested in accordance with the UPHOLSTERED FURNITURE ACTION COUNCIL Fabric Classification Test Method. The results are as follows:
Test Results
Vertical Char Lengths
20mm 18mm 18mm
Test Results
Class I
If there are any questions or when we can be of further assistance, please let us know.
Sincerely,
Karon S. Matkins
British Standards Institution
Fire Test for Furniture
(As Tested by Diversified Labs) see top of page
| Reference: |
Flammability Test Report
Lab Identification No. 3854
Invoice No. 8418 |
One (1) upholstery fabric sample, identified as Flame-No-More, 58% Rayon/20% Cotton/22% Polyester (9.8 oz./sq. yd.), was received and tested in accordance with BRITISH STANDARDS INSTITUTION "Fire Test for Furniture, 5852. Part 1. Methods of Test for the Ignitability by Smokers' Materials of Upholstered Composites for Seating." Per Section 10. (a), "The following test results relate only to the ignitability of the combination of materials under the particular conditions of test; they are not intended as a means of assessing the full potential fire hazard of the materials in use."
The sample submitted was tested to Section 9.3 Butane Flame Test. The results are as follows:
| Ignition Source |
Test Results |
| Butane Flame Source 1 |
#1 - No progressive smouldering or flaming |
| Butane Flame Source 1 |
#2 - No progressive smouldering or flaming |
The sample submitted therefore meets minimum requirements of the above standard when tested to butane flame ignition source 1.
If there are any questions or when we can be of further assistance, please let us know.
Sincerely,
Karon S. Matkins
Please note that the approval shown here is for Flame-No-More products.