Christmas Tree Lab Report
Please note that the approval shown here is for Flame-No-More product. FLAMETARD Christmas Tree product is the same product by the same manufacturer.
CONSOS, INC.
LABORATORY INSPECTION REPORT
P.O. BOX 34186
CHARLOTTE, N.C. 28234
PHONE: (704) 596-2613
PRODUCT: PINE TREE BRANCHES - AGED 30 DAYS
SPECIFICATION: CALIFORNIA TITLE 19 - CHRISTMAS TREES
IDENTIFICATION & QUANTITY: REPORT #CA12059
TESTING COMPLETED: DECEMBER 5, 1989
PLANT: CARECHEM CORPORATION, CARY, NC
| TEST METHODS |
RESULTS |
REQUIREMENTS |
| FLAME TEST
BRANCHES - TREATED
(TESTED AT 50% RELATIVE HUMIDITY)
|
| Spread of Flame |
After Flame |
Appearance |
| NO |
0.0 |
PASS |
| NO |
1.8 |
PASS |
| NO |
2.0 |
PASS |
| NO |
0.0 |
PASS |
| NO |
0.0 |
PASS |
| NO |
0.4 |
PASS |
| AVG. |
0.7 |
|
|
NO SPREAD OF FLAME:
AFTER FLAME: 10 SEC. MAX.
THE TREATED BRANCHES SHALL NOT LOSE ITS NEEDLES MORE READILY NOR SHALL THEY HAVE TURNED BROWN TO A GREATER EXTENT THAN THOSE ON THE UNTREATED BRANCHES SIMILARLY AGED.
|
I CERTIFY THAT THE ABOVE TESTS WERE PERFORMED UNDER MY SUPERVISION IN ACCORDANCE WITH THE SPECIFICATION TEST REQUIREMENTS AND THAT THE REPORTED TEST RESULTS ARE TRUE, VALID AND APPLICABLE TO THE SAMPLES TESTED. I FURTHER CERTIFY THAT THESE SAMPLES WERE THE ONLY SAMPLES TESTED FROM THE LOT IDENTIFIED ABOVE.
SUPERVISOR / BETH HERLOCKER
LABORATORY CHIEF / BILL WOLHAR
CONSOS, INC.
|